Steam & utilities · Free tool
Flash steam and condensate recovery calculator
Find how much flash steam forms when hot condensate passes through a steam trap into a lower-pressure line or flash vessel, how much heat it carries and what it is worth to recover.
1. Condensate
2. Flash vessel
15–25 m/s is typical for low-pressure steam
3. Value
Flash steam
281.2kg/h
14.06% of the condensate
Heat in flash steam
173.9kW
Value if recovered
₹44.55lakh/yr
| Condensate temperature in | 184.1 °C (hf 781.2 kJ/kg) |
|---|---|
| Flash vessel temperature | 111.6 °C (hf 468.2 kJ/kg) |
| Latent heat at flash pressure | 2,225.5 kJ/kg |
| Residual condensate | 1,718.8 kg/h |
| Flash steam volume | 323.4 m³/h |
| Flash steam line (Sch 40) | 80 NB, 18.8 m/s |
Want these numbers checked?
Send them to a SEMCO process engineer for a free review, sizing and budget price.
How this calculator works
Condensate leaving a trap is saturated at the steam pressure. When its pressure falls, it holds more heat than water can at the lower pressure, and the excess boils part of it into flash steam.
The flash fraction is the difference in liquid enthalpy between the two pressures divided by the latent heat at the lower pressure. Properties come from the same IAPWS equations as the steam table calculator.
Formulas used
Flash fraction
Assumptions and limits
- Condensate arrives saturated at the upstream pressure (no subcooling in the trap).
- No heat loss in the flash vessel.
- Value uses your steam cost per tonne and operating hours.
Worked example
2,000 kg/h of condensate from 10 bar(g) steam into a flash vessel at 0.5 bar(g).
- hf at 11 bar(a) ≈ 781 kJ/kg; hf at 1.5 bar(a) ≈ 468 kJ/kg; hfg at 1.5 bar(a) ≈ 2,226 kJ/kg.
- Flash fraction = (781 − 468) ÷ 2,226 ≈ 14.1%, so about 281 kg/h of flash steam.
- That is about 174 kW of heat, worth roughly ₹44 lakh a year at ₹2,200 per tonne over 7,200 hours.
Frequently asked questions
How much flash steam is produced from condensate?
Typically 5–20% by mass, depending on the pressure drop. From 10 bar(g) to atmospheric it is about 16%.
What can flash steam be used for?
Low-pressure heating such as feed-water and deaerator heating, space heating, preheating process liquids or the first effect of an evaporator.
How do I size a flash vessel?
Size the vessel so the flash steam's upward velocity is low enough for water droplets to separate, and the vent line for 15–25 m/s.
Need it designed and built?
SEMCO designs, fabricates and commissions evaporators, ZLD plants, heat exchangers, reactors and vacuum systems in its own factories in Pune and Solapur.
Related tools
Saturated steam table calculator
Temperature, pressure, enthalpy, latent heat and specific volume of saturated steam, in bar(g), bar(a), kg/cm² or psi.
Pipe insulation heat loss and thickness
Heat loss per metre, surface temperature and yearly steam cost for each insulation thickness.
Pipe sizing and pressure drop calculator
Velocity, Reynolds number, friction factor and pressure drop for liquids and steam, with recommended pipe size.
Results are engineering estimates for early sizing and budgeting. Final designs depend on your liquid, site and codes, and are confirmed in SEMCO's proposal. Method reviewed by Jogender Dhayal, Director, SEMCO.