Pumps, piping & valves · Free tool

Pipe sizing and pressure drop calculator

Pick a line size for water, process liquids, saturated steam or gas. Enter the flow and the calculator shows the velocity and pressure drop in each nearby pipe size, and suggests the smallest size within recommended velocity.

VelocityΔP per 100 mSuggested size

1. Fluid and flow

m³/h

2. Pipe

Schedule

m
%

Bends, valves, tees

Suggested size

80 NB

3 inch, Sch 40

Velocity

1.75m/s

Target 1–2.5 m/s

Pressure drop

0.498bar

over 130 m equivalent

SizeID mmVelocity m/sReynoldsΔP bar/100 m
50 NB (2")52.53.852,51,6162.856
65 NB (2 1/2")62.72.702,10,6841.153
80 NB (3")77.91.751,69,5750.383
100 NB (4")102.31.011,29,1290.098
125 NB (5")128.20.651,03,0410.032
Recommended velocity: 1–2.5 m/s for pump discharge; 0.6–1.2 m/s on pump suction. The suggested size is the smallest one within the upper limit; size up if pressure drop matters more than cost.

Density used 996 kg/m³, viscosity 0.8 cP, mass flow 29,880 kg/h. Target velocity midpoint 1.75 m/s.

Want these numbers checked?

Send them to a SEMCO process engineer for a free review, sizing and budget price.

Discuss on WhatsApp

How this calculator works

For each standard pipe size, the calculator divides the volumetric flow by the bore area to get the velocity. It then works out the Reynolds number from density, velocity, bore and viscosity, which tells whether the flow is laminar or turbulent.

The Darcy friction factor comes from the Swamee-Jain equation, an explicit form of the Colebrook equation, for turbulent flow, and 64/Re for laminar flow. The Darcy-Weisbach equation then gives the pressure drop. Fittings are added as a percentage of equivalent length.

For saturated steam the density is taken at your line pressure from the steam table calculator. Bore sizes follow ASME B36.10 (Schedule 40) and B36.19 (Schedule 10S).

Formulas used

Velocity

v=4QπD2

Reynolds number

Re=ρvDμ

Swamee-Jain friction factor (turbulent)

f=0.25[log10(ε3.7D+5.74Re0.9)]2

Darcy-Weisbach pressure drop

ΔP=fLDρv22

Assumptions and limits

  • Single-phase, incompressible flow. For steam and gas this holds when the pressure drop is under about 10 percent of line pressure.
  • Fittings are an allowance on length. For long or complex lines, add each fitting's equivalent length or K value.
  • Water properties at about 30 °C. Hot water has lower viscosity, which slightly reduces pressure drop.
  • Elevation changes, control valves and equipment pressure drops are not included.

Worked example

30 m³/h of cooling water through 100 m of carbon steel Sch 40 pipe with 30 percent extra for fittings.

  1. Try 80 NB (77.9 mm bore): area 0.00477 m², velocity = (30/3,600) ÷ 0.00477 ≈ 1.75 m/s, inside the 1–2.5 m/s range.
  2. Reynolds number = 996 × 1.75 × 0.0779 ÷ 0.0008 ≈ 170,000, turbulent.
  3. Friction factor from Swamee-Jain with 0.045 mm roughness ≈ 0.0196.
  4. Pressure drop ≈ 0.0195 × (130 ÷ 0.0779) × 996 × 1.75² ÷ 2 ≈ 0.50 bar over the line.

Frequently asked questions

What velocity should water flow at in a pipe?

About 1 to 2.5 m/s on pump discharge lines, and 0.6 to 1.2 m/s on pump suction to protect against cavitation. Long lines are often sized at the lower end to save pumping power.

What velocity is recommended for steam pipes?

Saturated steam mains are usually sized for 15 to 35 m/s. Higher velocities cause noise, erosion and large pressure drops; wet steam and condensate lines need lower velocities.

What is the difference between Schedule 40 and 10S?

They have the same outside diameter but different wall thickness. Schedule 40 is common for carbon steel; Schedule 10S is a thinner stainless steel pipe with a slightly larger bore.

Why does the pressure drop rise so fast with smaller pipe?

For a fixed flow, pressure drop rises roughly with the fifth power of the diameter going down. Going one size smaller can double or triple the pressure drop.

Need it designed and built?

SEMCO designs, fabricates and commissions evaporators, ZLD plants, heat exchangers, reactors and vacuum systems in its own factories in Pune and Solapur.

Results are engineering estimates for early sizing and budgeting. Final designs depend on your liquid, site and codes, and are confirmed in SEMCO's proposal. Method reviewed by Jogender Dhayal, Director, SEMCO.