Steam & utilities · Free tool
Cooling tower calculator
Calculate a cooling tower's evaporation loss, blowdown and make-up water, along with range, approach, effectiveness and heat load. Handy for water balances and ZLD planning.
1. Water circuit
2. Weather
Pune and Mumbai: 27–29 °C for design
3. Water chemistry
Make-up TDS × CoC = circulating TDS
Modern eliminators 0.001–0.02%
Make-up water
8.16m³/h
196 m³/day
Evaporation loss
6.12m³/h
Blowdown
1.94m³/h
46.6 m³/day to treat
| Range | 8 °C |
|---|---|
| Approach | 4 °C |
| Effectiveness range/(range + approach) | 66.7% |
| Heat rejected | 4,621 kW = 1,314 TR |
| Drift loss | 0.1 m³/h |
| Circulating water TDS | 1,600 mg/L |
Want these numbers checked?
Send them to a SEMCO process engineer for a free review, sizing and budget price.
How this calculator works
Each kilogram of water evaporated removes its latent heat, so evaporation is proportional to circulating flow and the temperature range. The common rule of 0.00153 × flow × range (°C) is used.
Dissolved solids stay behind when water evaporates. To hold the circulating water at a set cycles of concentration, part of it is bled off as blowdown. Make-up replaces evaporation, blowdown and drift.
Formulas used
Evaporation
Blowdown and make-up
Effectiveness
Assumptions and limits
- Evaporation rule of thumb based on a latent heat of about 2,400 kJ/kg and most heat removed by evaporation; actual evaporation varies a little with weather.
- Blowdown includes all bleed and leaks; drift is taken from your percentage.
- This does not size the tower itself (fill, fans); approach below 3 °C is flagged as uneconomic.
Worked example
500 m³/h cooled from 40 to 32 °C, wet-bulb 28 °C, 4 cycles of concentration, 0.02% drift.
- Range = 8 °C, approach = 4 °C, effectiveness = 67%.
- Evaporation = 0.00153 × 500 × 8 ≈ 6.1 m³/h.
- Blowdown = 6.1 ÷ 3 − 0.1 ≈ 1.9 m³/h; make-up ≈ 8.2 m³/h, about 196 m³ a day.
- Heat rejected ≈ 4,620 kW, about 1,310 TR.
Frequently asked questions
How much water does a cooling tower lose?
Roughly 1% of the circulating flow for every 7 °C of range is lost to evaporation, plus blowdown and drift.
What are cycles of concentration?
The ratio of dissolved solids in the circulating water to those in the make-up. Higher cycles save water and blowdown but raise scaling risk, so they depend on water treatment.
What is approach in a cooling tower?
The difference between the cold water temperature and the wet-bulb temperature. It cannot be zero; 4–6 °C is typical.
Need it designed and built?
SEMCO designs, fabricates and commissions evaporators, ZLD plants, heat exchangers, reactors and vacuum systems in its own factories in Pune and Solapur.
Related tools
Psychrometric calculator
Humidity ratio, relative humidity, wet-bulb, dew point and enthalpy of humid air at your site altitude.
ZLD plant sizing estimator
From effluent flow and TDS to RO reject, evaporator load, salt generated and daily running cost.
Heat exchanger LMTD and area calculator
Heat duty, missing outlet temperature, LMTD, F-correction and the heat transfer area you need.
Results are engineering estimates for early sizing and budgeting. Final designs depend on your liquid, site and codes, and are confirmed in SEMCO's proposal. Method reviewed by Jogender Dhayal, Director, SEMCO.