Heat exchanger LMTD and area calculator

Size a shell and tube, double pipe or plate heat exchanger for a first estimate. Enter the hot and cold streams, or heat with steam, and get the heat duty, LMTD, F-correction, the area you need and roughly how many tubes.

Duty kWLMTDArea m²Tubes

1. Hot side

Heating medium

kg/h
kJ/kg·K

Water 4.18, oils ~2.0

°C
°C

2. Cold side

Work out

kg/h
kJ/kg·K
°C

3. Exchanger

%

10–25% for fouling and uncertainty.

m

Area needed

19.3m²

16.8 m² + 15% margin

Heat duty

609.6kW

5,24,242 kcal/h

Corrected MTD

32.97°C

Details
Hot side95.0 → 60.0 °C
Cold side30,000 kg/h, 32.0 → 49.5 °C
Terminal differences45.50 °C and 28.00 °C
LMTD36.04 °C
F correction0.915 (R = 2.00, P = 0.278)
U used1,100 W/m²K
Tubes neededabout 54 tubes of 19.05 mm × 6 m

Want these numbers checked?

Send them to a SEMCO process engineer for a free review, sizing and budget price.

Discuss on WhatsApp

How this calculator works

The calculator first balances heat: what the hot stream gives up, the cold stream takes in. From the hot side flow, specific heat and temperatures it finds the duty, then works out either the cold outlet temperature or the cold flow you need. With condensing steam, the steam side stays at its saturation temperature and the steam flow is the duty divided by the latent heat.

It then calculates the log mean temperature difference (LMTD) from the temperature differences at the two ends. For a shell and tube exchanger with one shell pass and two or more tube passes, flow is partly co-current, so the LMTD is multiplied by the correction factor F from the Bowman, Mueller and Nagle equation.

Finally, area = duty ÷ (U × corrected MTD), plus your design margin. U comes from the typical range for the service you pick, or your own value.

Formulas used

Heat duty

Q=mhcp,h(Th,in−Th,out)=mccp,c(Tc,out−Tc,in)

Log mean temperature difference

LMTD=ΔT1−ΔT2ln(ΔT1/ΔT2)

F correction for 1 shell, 2+ tube passes

F=√R2+1 ln1−P1−PR(R−1)ln2−P(R+1−√R2+1)2−P(R+1+√R2+1)

R = (Th,in − Th,out) / (Tc,out − Tc,in), P = (Tc,out − Tc,in) / (Th,in − Tc,in).

Area

A=QU·F·LMTD

Assumptions and limits

  • Specific heats are constant over the temperature range. For large temperature changes, use the average value.
  • U values are typical ranges for clean-to-moderately fouled service. A detailed design calculates U from film coefficients, wall and fouling resistances.
  • With steam heating, the steam is dry saturated and condenses fully, with condensate leaving at saturation temperature.
  • Tube count uses the outside area of plain tubes and ignores tubesheet thickness.

Worked example

Cool 15,000 kg/h of hot water from 95 °C to 60 °C with 30,000 kg/h of cooling water at 32 °C in a 1-2 shell and tube exchanger.

  1. Duty = 15,000/3,600 × 4.18 × (95 − 60) ≈ 609.6 kW.
  2. Cooling water outlet = 32 + 609.6 ÷ (30,000/3,600 × 4.18) ≈ 49.5 °C.
  3. End differences: 95 − 49.5 = 45.5 °C and 60 − 32 = 28 °C, so LMTD ≈ 36.0 °C.
  4. R = 35 ÷ 17.5 = 2.0 and P = 17.5 ÷ 63 ≈ 0.28, giving F ≈ 0.915.
  5. With U = 1,100 W/m²K, area = 609,600 ÷ (1,100 × 0.915 × 36.0) ≈ 16.8 m², or about 19.3 m² with a 15 percent margin.

Frequently asked questions

What is a good U value for a shell and tube heat exchanger?

It depends on the fluids. Water to water is typically 800 to 1,500 W/m²K, condensing steam to water 1,500 to 3,500, oil coolers 150 to 500, and gas coolers only 20 to 100. Viscous liquids and fouling services are at the low end.

Why use a correction factor F?

In a multi-pass shell and tube exchanger, the flow is not purely counter-current, so the real mean temperature difference is lower than the LMTD. F, usually 0.8 to 1, accounts for this. Designs with F below about 0.75 to 0.8 are avoided.

What is a temperature cross?

When the cold outlet is hotter than the hot outlet. It is possible in pure counter-current flow but not in a single 1-2 shell; it then needs shells in series.

How much margin should be added to the area?

Commonly 10 to 25 percent, more for fouling liquids such as effluents, slurries or cooling water with poor treatment.