Psychrometric calculator
Get the properties of humid air from dry-bulb temperature plus relative humidity, wet-bulb or dew point, corrected for your site's altitude. Useful for dryers, cooling towers, HVAC and process air.
1. Air condition
Second property
2. Location
Pune ≈ 560 m, Mumbai ≈ 10 m
Humidity ratio
19.32g/kg dry air
Relative humidity
60%
Enthalpy
81.7kJ/kg dry air
| Wet-bulb temperature | 25.45 °C |
|---|---|
| Dew-point temperature | 23.26 °C |
| Specific volume | 0.9529 m³/kg dry air |
| Density of moist air | 1.0697 kg/m³ |
| Vapour partial pressure | 28.56 mbar |
| Atmospheric pressure at site | 0.9478 bar(a) |
Want these numbers checked?
Send them to a SEMCO process engineer for a free review, sizing and budget price.
How this calculator works
The calculator works out the water vapour partial pressure from your input, using the saturation pressure of water from the IAPWS equations. Humidity ratio, enthalpy and specific volume then follow from standard ASHRAE relations.
Wet-bulb is found by solving the ASHRAE psychrometric equation. Atmospheric pressure is estimated from altitude with the standard atmosphere model.
Formulas used
Humidity ratio
Enthalpy of moist air
Assumptions and limits
- Temperatures between 0 and 99 °C (water, not ice).
- Ideal-gas mixture of dry air and water vapour.
- Atmospheric pressure from altitude; enter 0 m for sea level.
Worked example
Air at 32 °C and 60% RH in Pune (560 m).
- Atmospheric pressure ≈ 0.948 bar; saturation pressure at 32 °C ≈ 47.6 mbar, so pw ≈ 28.6 mbar.
- W = 0.622 × 28.6 ÷ (948 − 28.6) ≈ 19.3 g/kg.
- Wet-bulb ≈ 25.5 °C, dew point ≈ 23.3 °C, enthalpy ≈ 82 kJ/kg dry air.
Frequently asked questions
What is the difference between wet-bulb and dew point?
Dew point is where air becomes saturated if cooled without adding moisture. Wet-bulb is the temperature reached by evaporating water into the air; it lies between dew point and dry-bulb.
Why does altitude matter?
Lower air pressure means the same vapour pressure gives a higher humidity ratio, which affects dryer and cooling tower calculations.
How is this used for dryer design?
The difference in humidity ratio between exhaust and inlet air, times the dry air flow, gives the water the dryer removes.
Need it designed and built?
SEMCO designs, fabricates and commissions evaporators, ZLD plants, heat exchangers, reactors and vacuum systems in its own factories in Pune and Solapur.
Read more
Related tools
Cooling tower calculator
Evaporation loss, blowdown and make-up water, with range, approach, effectiveness and heat load.
Process engineering unit converter
Pressure and vacuum (gauge and absolute), flow, energy, heat transfer coefficient, viscosity and more.
Saturated steam table calculator
Temperature, pressure, enthalpy, latent heat and specific volume of saturated steam, in bar(g), bar(a), kg/cm² or psi.
Results are engineering estimates for early sizing and budgeting. Final designs depend on your liquid, site and codes, and are confirmed in SEMCO's proposal. Method reviewed by Jogender Dhayal, Director, SEMCO.