Get the properties of humid air from dry-bulb temperature plus relative humidity, wet-bulb or dew point, corrected for your site's altitude. Useful for dryers, cooling towers, HVAC and process air.

g/kgWet-bulbDew pointEnthalpy

1. Air condition

Second property

%

2. Location

m

Pune ≈ 560 m, Mumbai ≈ 10 m

Humidity ratio

19.32g/kg dry air

Relative humidity

60%

Enthalpy

81.7kJ/kg dry air

Details
Wet-bulb temperature25.45 °C
Dew-point temperature23.26 °C
Specific volume0.9529 m³/kg dry air
Density of moist air1.0697 kg/m³
Vapour partial pressure28.56 mbar
Atmospheric pressure at site0.9478 bar(a)

Want these numbers checked?

Send them to a SEMCO process engineer for a free review, sizing and budget price.

Discuss on WhatsApp

How this calculator works

The calculator works out the water vapour partial pressure from your input, using the saturation pressure of water from the IAPWS equations. Humidity ratio, enthalpy and specific volume then follow from standard ASHRAE relations.

Wet-bulb is found by solving the ASHRAE psychrometric equation. Atmospheric pressure is estimated from altitude with the standard atmosphere model.

Formulas used

Humidity ratio

W=0.621945pwP−pw

Enthalpy of moist air

h=1.006 t+W(2501+1.86 t) kJ/kg dry air

Assumptions and limits

  • Temperatures between 0 and 99 °C (water, not ice).
  • Ideal-gas mixture of dry air and water vapour.
  • Atmospheric pressure from altitude; enter 0 m for sea level.

Worked example

Air at 32 °C and 60% RH in Pune (560 m).

  1. Atmospheric pressure ≈ 0.948 bar; saturation pressure at 32 °C ≈ 47.6 mbar, so pw ≈ 28.6 mbar.
  2. W = 0.622 × 28.6 ÷ (948 − 28.6) ≈ 19.3 g/kg.
  3. Wet-bulb ≈ 25.5 °C, dew point ≈ 23.3 °C, enthalpy ≈ 82 kJ/kg dry air.

Frequently asked questions

What is the difference between wet-bulb and dew point?

Dew point is where air becomes saturated if cooled without adding moisture. Wet-bulb is the temperature reached by evaporating water into the air; it lies between dew point and dry-bulb.

Why does altitude matter?

Lower air pressure means the same vapour pressure gives a higher humidity ratio, which affects dryer and cooling tower calculations.

How is this used for dryer design?

The difference in humidity ratio between exhaust and inlet air, times the dry air flow, gives the water the dryer removes.