Pumps, piping & valves · Free tool
Reynolds number calculator
Find the Reynolds number for flow in a pipe and see straight away whether it is laminar, transitional or turbulent, with the friction factor and pressure drop that go with it.
1. Flow
I know the
Carbon steel 0.045, stainless 0.015, PVC 0.0015
2. Fluid
Water 1 cP at 20 °C; air 0.018 cP
Reynolds number
90,621
Turbulent
Velocity
1.166m/s
Darcy friction factor
0.021
Fanning 0.00525
| Flow regime | Turbulent |
|---|---|
| Relative roughness ε/D | 0.000578 |
| Pressure drop per 100 m | 0.1828 bar |
| Entrance length (fully developed) | 2.3 m |
| Kinematic viscosity | 1.002 cSt |
Want these numbers checked?
Send them to a SEMCO process engineer for a free review, sizing and budget price.
How this calculator works
The Reynolds number compares inertial forces with viscous forces. It is density × velocity × diameter ÷ viscosity. Below about 2,300 flow in a pipe is laminar; above about 4,000 it is turbulent.
For laminar flow the Darcy friction factor is 64/Re. For turbulent flow the calculator uses the Swamee-Jain equation, an explicit form of the Colebrook equation that includes pipe roughness.
Formulas used
Reynolds number
Swamee-Jain friction factor
Assumptions and limits
- Full, circular pipe; for other shapes use the hydraulic diameter 4 × area ÷ wetted perimeter.
- Newtonian fluid with constant properties.
- The Fanning friction factor is one quarter of the Darcy factor shown.
Worked example
20 m³/h of water at 20 °C in an 80 NB Sch 40 pipe (77.9 mm bore).
- Area = π × 0.0779² ÷ 4 = 0.00477 m², velocity = 20/3,600 ÷ 0.00477 ≈ 1.17 m/s.
- Re = 998 × 1.17 × 0.0779 ÷ 0.001 ≈ 90,600: turbulent.
- With 0.045 mm roughness, f ≈ 0.021, giving about 0.18 bar per 100 m.
Frequently asked questions
What Reynolds number is turbulent?
In pipes, flow is usually laminar below Re 2,300, turbulent above about 4,000, and transitional in between.
What is the difference between Darcy and Fanning friction factors?
They describe the same friction with different conventions. The Darcy factor is four times the Fanning factor; laminar flow gives 64/Re (Darcy) or 16/Re (Fanning).
Does the Reynolds number apply to gases?
Yes. Use the gas density and viscosity at line conditions; gas viscosities are around 0.01–0.02 cP.
Need it designed and built?
SEMCO designs, fabricates and commissions evaporators, ZLD plants, heat exchangers, reactors and vacuum systems in its own factories in Pune and Solapur.
Related tools
Pipe sizing and pressure drop calculator
Velocity, Reynolds number, friction factor and pressure drop for liquids and steam, with recommended pipe size.
Pump head, power and NPSH
Total head, shaft power, motor size and NPSH available for a centrifugal pump.
Particle settling velocity
Terminal settling velocity from Stokes to Newton regimes, for clarifiers and crystallisers.
Results are engineering estimates for early sizing and budgeting. Final designs depend on your liquid, site and codes, and are confirmed in SEMCO's proposal. Method reviewed by Jogender Dhayal, Director, SEMCO.