Control valve Cv and Kv sizing calculator
Size a control valve for liquid, gas or steam service. The calculator gives the required Kv and Cv, checks for choked flow and cavitation, and suggests a typical globe valve size.
1. Service
Fluid
2. Flow and conditions
Globe 0.85–0.9, ball 0.6, butterfly 0.55–0.7
Required Kv
21.21m³/h
Required Cv
24.52US
Typical globe valve
2"
Full-open Cv about 50
| Pressure drop | 2 bar |
|---|---|
| Choked-flow limit ΔP | 5.657 bar |
| Cv = 1.156 × Kv | 24.52 |
| Cv to select (+25% so the valve runs about 70–80% open) | 30.7 |
Want these numbers checked?
Send them to a SEMCO process engineer for a free review, sizing and budget price.
How this calculator works
Kv is the flow of water in m³/h through a valve with a 1 bar pressure drop; Cv is the US equivalent in gallons per minute at 1 psi. Cv = 1.156 × Kv.
For liquids, Kv follows from flow, specific gravity and pressure drop. If the pressure drop exceeds the choked limit set by the valve's recovery factor FL and the liquid's vapour pressure, the choked value is used and a cavitation warning is shown.
For gas and steam the standard (Samson/IEC-style) formulas are used, with separate subcritical and critical (sonic) forms. Critical flow starts when the pressure drop reaches about half the inlet absolute pressure.
A valve is normally selected with about 25% more Cv than required, so it controls at roughly 70–80% open.
Formulas used
Liquid
Gas, subcritical
Critical: Kv = QN ÷ (257 P1) × √(ρN T1). Pressures in bar(a), T in K.
Steam, subcritical
W in kg/h, v₂ the specific volume in m³/kg.
Assumptions and limits
- Turbulent, non-viscous flow; viscous liquids need a Reynolds-number correction.
- Piping geometry factor Fp = 1 (valve the same size as the line).
- Steam is dry saturated.
- Valve Cv values shown are typical for single-seat globe valves; use the manufacturer's tables for the final selection.
Worked example
30 m³/h of water, 6 bar(g) in and 4 bar(g) out, globe valve FL = 0.9.
- ΔP = 2 bar, well below the choked limit of about 5.7 bar.
- Kv = 30 × √(1/2) ≈ 21.2 m³/h; Cv ≈ 24.5.
- With 25% margin, select a valve with Cv ≈ 31: typically a 2" globe valve with reduced trim, or a 1½" full-trim valve.
Frequently asked questions
What is the difference between Cv and Kv?
Both measure valve capacity. Kv is in m³/h of water at 1 bar drop; Cv is in US gpm at 1 psi drop. Cv = 1.156 × Kv.
Why should a control valve not be oversized?
An oversized valve works near its seat, where small movements cause big flow changes, so control becomes unstable and the trim wears faster.
What is choked flow in a valve?
For liquids, it is when the pressure in the valve's throat falls to the vapour pressure and vapour forms; further pressure drop no longer increases flow and cavitation damage can start. For gases, it is sonic velocity in the throat.
Need it designed and built?
SEMCO designs, fabricates and commissions evaporators, ZLD plants, heat exchangers, reactors and vacuum systems in its own factories in Pune and Solapur.
Related tools
Safety valve sizing (API 520)
Required relief orifice area and API 526 orifice letter for gas, steam and liquid.
Orifice plate flow calculator
Flow through an orifice from ΔP, or the bore for a target flow, for liquids and gases.
Pipe sizing and pressure drop calculator
Velocity, Reynolds number, friction factor and pressure drop for liquids and steam, with recommended pipe size.
Results are engineering estimates for early sizing and budgeting. Final designs depend on your liquid, site and codes, and are confirmed in SEMCO's proposal. Method reviewed by Jogender Dhayal, Director, SEMCO.